Tutorial: Mechanic - electrician
Topic: Basics of electrical engineering the 2nd. year
Protection in electric networks
Prepared by: Škarka Miloš
Projekt Anglicky v odborných předmětech, CZ.1.07/1.3.09/04.0002
je spolufinancován Evropským sociálním fondem a státním rozpočtem
České republiky.
Injury by electric current – physiological effect of electric current coming through a body of a person or an animal
Basic protection – protection against an injury by electric current in a failure-free state
Protection in the case of a malfunction – protection against an injury by electric current during one malfunction
Dangerous animate part – an animate part, which could cause an injury by electric current in certain conditions
Basic insulation – insulation of dangerous animate parts providing basic protection
Additional insulation – separate insulation used for basic insulation, to provide protection in case of a malfunction
Double insulation – insulation containing basic and additional insulation
Links – electric connections between conductive parts for potential balancing
Animate part – conductor of conductive parts designed for voltage in normal operation including the central conductor
Inanimate part is conductive part of an electric device, which can be touched and where there is usually no voltage, but where can a dangerous contact voltage occur because of a malfunction (for example metal casing of a distributor).
Dangerous contact voltage is voltage (or a variance of potentials), which can cause an injury by electric current to a person or an animal contacting an inanimate part during a malfunction. Its size depends on the type of environment, in which this contact occurs (ČSN 33 2000-4-41).
Allowed contact voltage is a part of
grounding system voltage opposite to the
ground, which can be crossed over by a
human in distance from hands to feet
(horizontally 1m).
Amount of the allowed contact voltage depends not only on a purpose of its use and on an environment, but even on a duration of a malfunction. The shorter the duration of the contact voltage is, the higher the contact voltage can be.
Allowable values of the permanently allowed contact voltage at the device up to 1000V are mentioned in the following chart.
Environment contact with parts (in operation)
Safe low voltage of animate parts [V]
Alternating Direct
Normal Animate 50 100
Inanimate 50 120
Dangerous *) Animate 25 60
Inanimate 50 120
Extremely Dangerous
Animate 12 25
Inanimate 25 60
*) It can be also specified differently in the regulation, if the sum of conditions (determining or influencing danger of an injury caused by an electric current) demands it
Normal – ordinary; cold; dusty (if dust is not conductive and not flammable). Its character prevents an injury by electric current.
Dangerous – hot, wet (even temporarily), dusty (if dust is conductive and not flammable with increased corrosive aggression), with shocks, outdoor places with mechanical damage and conductive environment. These are those places, where there is a temporary or permanent danger of an injury caused by electric current because of external effects.
Extremely dangerous – wet, with extreme corrosive aggression, places, where there is danger of an injury greatly increased by adverse conditions (water, kettles and metal tanks, narrow spaces with metal materials, healthcare facilities or special regulations for specific protection). The danger of an injury is even more increased because of special conditions and outer effects
Protection against a dangerous contact with animate parts
Prevents passing of electric current through a body of a person or an animal, or the current is reduced to the safe amount
Protection against a dangerous contact with inanimate parts
Prevents passing of electric current through a body of a person or an animal, or the current is reduced to the safe amount or the device in case of a malfunction automatically disconnects from the source.
Protection against a dangerous contact with animate and inanimate parts
Voltage in animate parts can never exceed the safe amount
-
Inanimate part Dangerous contact voltage Allowed contact voltage of inanimate parts
types of environment Give examples
www.wikipedia.cz www.vosaspsekrizik.cz/cs/download/padesat
ka/ochrana-dotyk.pdf Elektro v praxi, 1 část, Solid Team