Environmental Engineering
Water based heating systems
Ing. Ondrej Hojer, Ph.D.
Fakulta strojníÚstav techniky prost ředí
1
2
3.11.2014
4
7
[email protected] Engineering
8
[email protected] Engineering
Heat sources
Fossil fuelsGas
Coal (Charcoal)Oil
Wood (Plants)
Electricity
Nuclear
SunGround
AirWater
Heat generator (transformer)
Boiler
Boiler, Heating coil
Turbine (waste heat)
Heat pump
3.11.2014
5
9
[email protected] Engineering
10
TABLE OF CONTENTS
• Pressure drop (Local and Friction)• Types of distribution heating systems• The neutral point• Control of the system
[email protected] Engineering
3.11.2014
6
11
[email protected] Engineering
PRESSURE DROP
A flow in pipe systems is associated with pressure losses. The total pressure drop consists of local pressure drop and friction p ressure drop.
FLt ppp ∆+∆=∆
12
[email protected] Engineering
∑ ⋅⋅=∆ ρζ2
2wpL
ζ = local loss coefficient [-],w = flow velocity in a characteristic cross-section S [m/s],ρ = fluid density [kg/m3],
where ρ⋅=∆2
2wpd is dynamic (velocity) pressure.
Local pressure drop
3.11.2014
7
13
[email protected] Engineering
101000
1002
ρρ ⋅
=∆⇒⋅
∆⋅=
vL
Lv k
Vp
pVk
&&
Local pressure drop - Valve
14
[email protected] Engineering
3.11.2014
9
[email protected] Engineering
where f is the friction factor ε is average absolute roughness of the pipe [m]Re is Reynolds number
Colebrook equation
where ρ is the density of the fluidV is the average velocity in the pipef is the friction factor from the Moody chartl is the length of the piped is the pipe diameter.
17
Friction pressure drop
ρ⋅⋅⋅=∆2
2w
d
lfp f
18
[email protected] Engineering
where:d = inside diameter [m],w = velocity [m/s],ν = kinematic viscosity [m2/s], (at 70°C, 0,415.10-6 m2/s)
νdw ⋅=Re
Reynolds number
3.11.2014
12
[email protected] Engineering 23
8000
40000
1500
4500
15°C
20°C 20°C 20°C 20°C20°C
-12°C
N
h = 3m
-106- -105- -104- -103- -102-
-101-BB
Water based Heating System – Design of a Panel radia tor
1x flow chamber
1x metal lamellas layer
TYPE 11
2x flow chamber
1x metal lamellas layer
TYPE 21
2x metal lamellas layer
TYPE 22
2x flow chamber
24
[email protected] Engineering
Design of a Panel Radiator
10 up 15 cm
10 up 15 cm
1000 mm
800
mm
Panel radiatorPanel radiator
500
mm
tw1 = 50 °C tw2 = 40 °C t i = 20 °C
3.11.2014
13
[email protected] Engineering 25
Nominal thermal output Q [W]
[email protected] Engineering 26
Nominal thermal output Q [W]
3.11.2014
14
[email protected] Engineering 27
Nominal thermal output Q [W]
[email protected] Engineering 28
Nominal thermal output Q [W]
3.11.2014
15
29
[email protected] Engineering
30
[email protected] Engineering
The bigger the t w1 – tw2 difference the smaller c value
3.11.2014
17
33
[email protected] Engineering
[email protected] Engineering 34
8000
40000
1500
4500
15°C
20°C 20°C 20°C 20°C20°C
-12°C
N
h = 3m
-106- -105- -104- -103- -102-
-101-BB
Water based Heating System – Design of tube diameter s
Section L [m]
m [kg/h]
dopt[mm]
wREAL[m/s]
R [Pa/m]
DpF = R . L [Pa]
Z = r . w2 / 2[Pa]
z [-]
DpL =Z . z[Pa]
1
2
3
...
wopt = 0.5 m/s friction local
Q = c . m . (t1-t2)[W] = [J/kg/K] . [kg/s] . [K]
Heat output mass flow
w = m / r / (p.d2/4)[m/s] = [kg/s] / [kg/m3] / [m2]
3.11.2014
18
[email protected] Engineering 35
FRICTION PRESSURE LOSSES – IRON TUBES
kg/hkg/h
Pa/mPa/m
m/sm/s
dimensions
roughness
[email protected] Engineering 36
LOCAL PRESSURE LOSSES – IRON TUBES
Main parts z [-]
Boiler cast iron 2.50
Boiler steel 2.00
Element radiator related to pipe DN 152.50
Panel radiator – 1 flow chamber related to pipe DN 158.50
Panel radiator – 2 and more flow chambers
related to pipe DN 1519.00
3.11.2014
19
[email protected] Engineering 37
LOCAL PRESSURE LOSSES – IRON TUBES
sidewalk
by-pass
T-part sharp
T-partaskew - separation
T-partaskew - conjunction
Reduction - fluent
Reduction - fluentbroadening
Flange connection
[email protected] Engineering 38
LOCAL PRESSURE LOSSES – IRON TUBES
Elbow - Bend
Collector
Distributorwith edges treatment
without edges treatmentwith radius edges
3.11.2014
20
39
[email protected] Engineering
Types of distribution heating systems
40
[email protected] Engineering
3.11.2014
21
41
[email protected] Engineering
42
[email protected] Engineering
According to the circulation of heat transfer medium• gravity heating systems• pump (forced) heating systems
According to the main-horizontal feed of heat transfer medi um• two-pipe down feed system• two-pipe up feed system
According to the circulation of heat transfer medium toward s heatingappliances• vertical heating system• horizontal heating system• stellate heating system
3.11.2014
22
43
[email protected] Engineering
Gravity heating systemsThe boiler is located at the lowest point in the system. The warm water has a lower density (it is lighter) than the cooled return water. Therefore, water in the system automatically starts circulate due to buoyant pressure. There is no need for a pump. As there is only a small differential pressure, wide-diameter pipes are required.
Pump (forced) heating systemsThe location of boilers and radiators is not important. Pressure losses are largely covered by pump pressure. Wide-diameter pipes are much smaller than by gravity systems.
Two-pipe down feed systemThis is the most common type of system. The flow and return main-horizontal pipes are routed under the ceiling of the cellar or basement. The radiators are connected to the vertical risers (max. two radiators to one riser in one floor).
Two-pipe up-feed systemIn this system the main-horizontal distribution pipe is above the level of the highest radiators. If circulating pump is used, both the flow pipe and the common return pipe can be located above the highest radiators.
44
[email protected] Engineering
Vertical heating systemThere is distribution with risers (vertical distribution pipes) and there must beconnected at most two radiators to one riser in one floor. The vertical system is themost common type of system at family houses and prefabs or apartment buildings.
Horizontal heating systemThere is distribution with minimal number of risers because the radiators areconnected on floor horizontal distribution pipes. Thus each apartment or each floorcan be fitted with its own heat meter.
Stellate heating systemThe riser is placed in the centre of disposition with distributor. Circuit of eachradiator is connected at the distributor. There are used pipe systems from plastics.
3.11.2014
23
45
[email protected] Engineering
Stellate heating system
46
[email protected] Engineering
According to the circulation of heat transfer medium• gravity heating systems• pump (forced) heating systems
According to the main-horizontal feed of heat transfer medi um• two-pipe down feed system• two-pipe up feed system
According to the circulation of heat transfer medium toward s heatingappliances• vertical heating system• horizontal heating system• stellate heating system• mixed heating system
According to the layout (supply and drain of heat transfer me dium toradiators)• two-pipe heating systems with counter-flow (normal) layout• two-pipe heating systems with concurrent-flow (Tichelmann; reversed return)layout•single-pipe heating systems without bypass of radiators (with four-way valves)•single-pipe heating systems with bypass of radiators (with riding connection)
3.11.2014
24
47
[email protected] Engineering
According to the contact with atmosphere• open vent heating systems• sealed (closed) heating systems
According to the material of a pipe system• pipe system from steel• pipe system from copper• pipe system from plastics (e.g. reticulate polyethylene PEX)• pipe system from multi-layer pipes
48
[email protected] Engineering
Mixed heating systemMixed heating system represents possibilities to combine one system to eachother. As for combination, mostly it is vertical heating system and horizontalheating system or two-pipe heating system with counter-flow layout andTichelmann two-pipe heating system.
Counter-flow system (two-pipe heating systems with counte r-flow layout)The return pipes have opposite flow than feed pipes. The length of radiatorcircuits is transformed in according to the distance of radiators in the system. Thepipe net must be hydraulically balanced. Each of parallel hydraulic circuit has tohave the same pressure loss with required mass flow.
Tichelmann system (two-pipe heating systems with co ncurrent-flow layout)The pipes are routed in such a way that the overall length of the radiators circuit is the same for each radiator. Hence, the same hydraulic pressure conditions apply to every radiator. Several boilers, risers or hot water storage tanks are connected in accordance with the Tichelmann layout. This method of connection is especially important with solar panels.
3.11.2014
25
49
[email protected] Engineering
Tichelmann connection systemStandard two-pipe connectionsystem
50
[email protected] Engineering
Single-pipe heating systems without bypass of radia tors (with four-way valves)Single-pipe heating systems with four-way valves have smaller transfer ability than systems with riding connection. The radiators can be connected in one or two points according to the kind of valves.
3.11.2014
26
51
[email protected] Engineering
Single-pipe heating systems with bypass of radiator s (with riding connection)These single-pipe systems consist of master pipe to which the radiators are connected with their flow (“feed”) and return in parallel. This enables the heating water to continue through the master pipe in circuit even if individual radiators are completely shut off. As with two-pipe systems, a single-pipe heating system can be constructed as a vertical or horizontal system. The vertical system was sometimes used in high-rise building.
[email protected] Engineering 52
Pump design
3.11.2014
27
[email protected] Engineering 53
http://www.jacpumps.com/pump_school_10.html
[email protected] Engineering 54
Dr. Lev Nelik. Buying a Bigger Pump May Bring Bigger Problems. Available online: http://www.pumpsandsystems.com/topics/pumps/buying-bigger-pump-may-bring-bigger-problems
Pump design
New Old
3.11.2014
28
[email protected] Engineering 55
Dr. Lev Nelik. Buying a Bigger Pump May Bring Bigger Problems. Available online: http://www.pumpsandsystems.com/topics/pumps/buying-bigger-pump-may-bring-bigger-problems
Pump design
New Old
56
[email protected] Engineering
THE NEUTRAL POINT
The position of the expansion vessel and circulating pump in a system defines pressure conditions. Low pressure – risk of air suction into the system. High pressure – risk of construction pressure of particular parts of heating system.
3.11.2014
29
57
[email protected] Engineering
Control valve – 2 way (quantitative control)
75 °C 75 °C
Boiler
panel radiator
M
65 °C65 °C
58
[email protected] Engineering
Control valve – 3 way (qualitative control)
75 °C70 °C
65 °C
Boiler
panel radiator
M
65 °C65 °C
3.11.2014
30
59
[email protected] Engineering
Control valve – possible connection variants
60
[email protected] Engineering
Control valve – possible pressure diagram
Overpressure diagram
System